Manual 2100-450L
Page 12 of 14
A call for 1st stage cooling or heating cycles the
compressor, and the dampers reposition to the
Potentiometer #2 setpoint. A call for 2nd stage
cooling or heating energizes compressor solenoid
FIGURE 6
CALL FOR COMPRESSOR OR FAN ONLY
WITH VENTILATION OFF
and repositions the damper blade to the Potentiometer
#3 position. On loss of blower operation, CRV closes
fully. See Figure 6.
Return Air
Supply Air
Coil
Condenser
Coil
Damper Blade
Evaporator
Condenser Air
Direction
MIS-2031 A