Manual 2100-449A
Page 1 of 13
INSTALLATION INSTRUCTIONS
ECONOMIZERS WITH EXHAUST
Models
EIFM-3C
For Use with Bard 2-1/2 through 3 Ton
Wall Mount Air Conditioners
and Heat Pumps
Produced in 2005 and Later
Manual : 2100-449A
Supersedes: 2100-449
File: Volume III Tab 19
Date: 03-14-08
Bard Manufacturing Company, Inc.
Bryan, Ohio 43506
Since 1914...Moving ahead, just as planned.
© Copyright 2004
Vue de la page 0
1 2 3 4 5 6 ... 12 13

Résumé du contenu

Page 1 - Bryan, Ohio 43506

Manual 2100-449APage 1 of 13INSTALLATION INSTRUCTIONSECONOMIZERS WITH EXHAUSTModelsEIFM-3CFor Use with Bard 2-1/2 through 3 TonWall Mount Air Condit

Page 2 - CONTENTS

Manual 2100-449APage 10 of 13ECONOMIZER – WA, WL & WH SERIESFEATURES•One piece construction – easy to install with nomechanical linkage adjustme

Page 3 - DESCRIPTION

Manual 2100-449APage 11 of 13CONDITION B – WARM OUTDOORSFirst stage cooling cycles and compressor and dampersremain in mechanical cooling mode.FIGURE

Page 4 - WARNING

Manual 2100-449APage 12 of 13FIGURE 8ECONOMIZER OPERATIONFOR SINGLE COMPRESSOR UNITWALL THERMOSTATSFOR HEAT PUMPS WITH ECONOMIZERThermostat Part 8403

Page 5 - Page 5 of 13

Manual 2100-449APage 13 of 13

Page 6 - Page 6 of 13

Manual 2100-449APage 2 of 13CONTENTSGENERALGeneral Information ... 3Unpacking...

Page 7 - Page 7 of 13

Manual 2100-449APage 3 of 13GENERALGENERAL INFORMATIONThe economizer should only be installed by a trainedheating and air conditioning technician. Th

Page 8 - TOP VIEW OF CONTROL PANEL

Manual 2100-449APage 4 of 132. Remove and save the existing exterior bloweraccess and service access panels on the Bard wallmount unit. (See Figure 1

Page 9 - Page 9 of 13

Manual 2100-449APage 5 of 134. Remove and discard the condenser partition blankoff plate. (See Figure 2.)3. RIGHT HAND UNITS Remove and save existin

Page 10 - Page 10 of 13

Manual 2100-449APage 6 of 135. FOR RIGHT HAND UNITS Install economizerby inserting the economizer into the unit to the farleft side clearing the rig

Page 11 - MECHANICAL COOLING OPERATION

Manual 2100-449APage 7 of 136. Mount mixed air thermistor to blower partition asshown with screws provided. Bracket with sensorinstalls on top of blo

Page 12 - WALL THERMOSTATS

Manual 2100-449APage 8 of 13FIGURE 5TOP VIEW OF CONTROL PANEL

Page 13 - Page 13 of 13

Manual 2100-449APage 9 of 139. Connect lead with fork terminal to correspondingpoints on terminal strip. Re.: C.Y.G. (See wiringdiagram.)10. Wire nut